Understanding the Fail-Safe Concept
|
||
| Principle of Safety The fail-safe concept monitors the sensor status at all times. In the event of a failure, the fail-safe concept will simulate a protected position. The ˇ§protectedˇ¨ position is when the sensor is activated (closed) and the ˇ§normalˇ¨ or ˇ§runˇ¨ position is when the sensor is not activated (open). |
||
![]() |
||
| - Normal Conditions ˇV constant current flow (I) holding relay coil (K1)
energized - Loss of Power ˇV no current flow (I) and relay coil (K1) is de-energized - Actuation of Sensor ˇV relay coil (K1) is shorted and de-energized - Failure of Sensor in the closed position ˇV relay coil (K1) is shorted and de-energized - Failure of Sensor in the open position ˇV (broken wire, switch or conductor) interupts current flow (I) and relay coil (K1) is de-energized - Resistor R ˇV limits current flow through the sensor when actuated |
||
| Fail-Safe (4 wire system) | ||
|
||
| In addition to the safety aspects achieved with Fail-Safe, it also provides: | ||
| - Isolation of the machine controls and sensor(s) - Isolation of high amperage and high voltage machine switching from the low voltage sensors - Conversion of a normally open switch to required normally closed machine controls |